Danfoss VLT 2800 Operations Instructions

Browse online or download Operations Instructions for Power adapters & inverters Danfoss VLT 2800. Danfoss VLT 2800 Operating instructions User Manual

  • Download
  • Add to my manuals
  • Print

Summary of Contents

Page 1 - VLT® 2800

VLT® 2800 The Quick GuideMAKING MODERN LIVING POSSIBLEPhone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Emai

Page 2 - 1Quick Guide

VLT 2880 - VLT2882Fit screened/armoured cable from the motor to the motor terminals of the frequency converter,i.e. U, V, W. The screen ends in a sc

Page 3 - 1.1.4 Use on Isolated Mains

1.4.4 Motor connection Connect the motor to terminals 96, 97, 98. Connect earth to terminal 99.See Technical data for correct dimensioning of cable cr

Page 4 - 1.2 Introduction

1.4.6 Motor Cables See General Specifications for correct dimensioning of motor cable cross-section and length. SeeEMC Emissions for relationship betw

Page 5 - 1.3 Mechanical Installation

No. Function01-03 Relay outputs 01-03 can be used for indicating status and alarms/warnings.12 24 V DC voltage supply.18-33 Digital inputs.20, 55 Comm

Page 6

Connect all earthing systems to ensure the lowest possible conductor impedance. The lowestpossible conductor impedance is achieved by keeping the cond

Page 7 - 1.3.3 IP 21 solution

1.4.11 Extra protection RCD relays/ELCBs, multiple protective earthing or earthing can be used as extra protection, pro-vided that local safety regula

Page 8

1.4.13 FusesBranch circuit protection:In order to protect the installation against electrical and fire hazard, all branch circuits in an in-stallatio

Page 9 - 1.4 Electrical Installation

Alternative fuses 380-500 V drivesVLT2800Buss-mannE52273Buss-mannE4273Buss-mannE4273Buss-mannE4273Buss-mannE4273Buss-mannE4273SIBAE180276LittleFuseE81

Page 10 - 1.4.3 Mains connection

1.5 Programming1.5.1 Control UnitOn the front of the frequency converter thereis a control panel divided into four sections.1. Six-digit LED display.

Page 11 - 1.4.4 Motor connection

NB!If the [STOP/RESET] key is set at Not active [0] in parameter 014 Local stop/re-set, and there is no stop command via the digital inputs or serial

Page 12 - 1.4.8 Control Cables

1Quick Guide1.1 Safety1.1.1 WarningsHigh Voltage Warning:The voltage of the frequency converter is dangerous whenever it is connected tomains. Incorre

Page 13 - 1.4.9 Earthing

1.5.7 Hand AutoDuring normal operation the frequency converter is in Auto mode, where the reference signal isgiven externally, analog or digital via t

Page 14 - 1.4.10 EMC emission

NB!VLT 2880-2882 do not have the AMT function.Set reference rangeMin. reference, RefMINParameter 204Max. reference, RefMAXParameter 205Set ramp timeRa

Page 15 - 1.4.11 Extra protection

1.7 Connection ExamplesMore examples can be found in the Operating Instructions (MG.27.AX.YY). 1.7.1 Start/Stop Start/stop using terminal 18 and coast

Page 16 - 1.4.13 Fuses

Parameter Overwiev0-XX Operation/Display0-01 Language*[0] English[1] German[2] French[3] Danish[4] Spanish[5] Italian002 Local/Remote Operation*[0] Re

Page 17 - 1.4.14 RFI switch

121 Start Function[0] DC hold during start delay time[1] DC brake during start delay time*[2] Coasting during start delay time[3] Start frequency/volt

Page 18 - 1.5 Programming

[16] Speed up[17] Speed down[19] Catch up[20] Slow down[21] Ramp 2[22] Preset ref, LSB[23] Preset ref, MSB[24] Preset reference on[25] Thermistor[26]

Page 19 - 1.5.6 Quick menu

405 Reset Function*[0] Manual reset[1] Automatic reset x 1[3] Automatic reset x 3[10] Automatic reset x 10[11] Reset at power-up406 Automatic Restart

Page 20 - 1.5.7 Hand Auto

1.9.1 Warnings/alarm messages No. Description W A T Cause of Problem2 Live zero error (LIVE ZEROERROR)X X X Voltage or current signal on terminals 53

Page 21 - 1.6 Motor Start

No. Description W A T Cause of Problem50 AMT not possible X Either RS value is outside permitted limits, ormotor current is too low on at least on

Page 22 - 1.8 Parameter List

1.10 Specifications1.10.1 Mains Suply 200 - 400 VAccording to . internationalstandardsType 2803 2805 2807 2811 2815 2822 2822PD22840 2840PD2Output cur

Page 23 - Load and Motor

1.1.2 Safety Instructions• The frequency converter must be disconnected from the mains if repair work is to becarried out. Check that the mains supply

Page 24 - MG.28.M1.02 - VLT

According to internationalstandardsType 2840 2855 2875 2880 2881 2882Output current IINV. [A] 9.1 12 16 24 32.0 37.5(3 x 380-480V)IMAX (60s) [A] 14.5

Page 25 - Special Functions

Control card, digital inputs:Number of programmable digital inputs 5Terminal number 18, 19, 27, 29, 33Voltage level 0 - 24 V DC (PNP positive logic)Vo

Page 26

Accuracy on frequency output Max. error: 0.2 % of full scaleResolution on frequency output 10 bitThe digital output is galvanically isolated from the

Page 27

Max. cross section to control wires, rigid wire 1.5 mm2/16 AWG (2 x 0.75 mm2)Max. cross section to control cables, flexible cable 1 mm2/18 AWGMax. cro

Page 28 - Motor thermal protection

cabinet fitting with fresh-air circulation in the cabinet is recommended, thereby ensuring thataggressive gases are kept away from the frequency conve

Page 29 - 1.10 Specifications

1.2 IntroductionUse this Quick Guide to carry out quick andEMC-correct installation of the frequency con-verter in five steps.Read the safety section

Page 30 - 1.11 General Specifications

Title Literature no.VLT 2800 Operating Instructions MG.27.AX.YYVLT 2800 Design Guide MG.27.EX.YYVLT 2800 Data Sheet MD.27.AX.YYMounting Instruction fo

Page 31

NB!With the IP 21 solution all units require a minimum of 100 mm air on each side. Thismeans that side-by-side mounting is NOT allowed.Size mm A a B b

Page 32

1.3.2 Terminal cover The drawing below gives the dimensions for NEMA 1 terminal covers for VLT 2803-2875.Dimension 'a' depends on the unit

Page 33 - 1.12 Special Conditions

1.3.4 EMC filter for long motor cablesFilter Dimensions192HA719A B C øa D E F G20 204 20 5.5 8 234 27.5 244H I øb J K L M N7545 6 190 60 16 24 12192H

Page 34

1.4 Electrical Installation1.4.1 Electrical Installation in GeneralNB!All cabling must comply with national and local regulations on cable cross-secti