4
VMIFB202
Hot gas temperature too high
See in service under heat pump also check using own digital thermometer.
Action:
Check the refrigerant circuit see section below
The discharge pipe sensor displays correctly but still has high overheating
Action:
Using manometer apparatus and a digital thermometer check what the cooling and overheating reading of the unit is.
Also check that bulb and capillary tube are undamaged and that the bulb is correctly positioned. (Bulb is positioned at two o’clock in
the suction pipe).
If the cooling is correct according to the instructions try adjusting the overheating using the expansion valve, if the overheating cannot
be adjusted using the expansion valve or if the capillary tube or bulb are damaged replace it.
Lack of refrigerant, not enough refrigerant in the hp cooling circuit.
Action:
Using manometer apparatus and a digital thermometer, check that the unit’s cooling and overheating is correct for the specic
refrigerant.
If cooling is not at the correct level compared with the specic refrigerant and is too low, there is insucient refrigerant in the unit.
If there appears to be a leak in the refrigerant circuit, carry out leak tracing and any necessary corrective action. If leak tracer is not
available, brush soap water on the suspected leak and look for bubbles.
Also check if oil has leaked. In event of leakage oil usually comes from the refrigerant circuit.
Troubleshooting Guide Working pressostat and high pressure pipe
Discharge
pipe sensor
location
temperatur ohm
-30 1884
-25 1443
-20 1115
-15 868
-10 681
-5 538
0 428
5 343
10 276
15 224
20 183
25 150
30 124
35 103
40 86
temperatur kohm
0 66.3
5 52.4
10 41.8
15 33.5
20 27.1
25 22
30 18
35 14.8
40 12.2
45 10.1
50 8.5
55 7.1
60 6
65 5
70 4.2
75 3.7
80 3.1
85 2.7
150 ohm sensor
Outdoor / Defrost sensor
22 kohm sensor
Supply line, return line, hot water,
brine in, brine out, discharge pipe sensor
Page view 3
1 2 3 4 5 6 7 8 9 ... 33 34

Comments to this Manuals