Danfoss VLT 6000 Service Manual Page 3

  • Download
  • Add to my manuals
  • Print
  • Page
    / 28
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 2
VLT
®
6000 HVAC
Introduction to
HVAC
175HA490.13
Warning:
Touching the electrical parts may be fatal - even after the equipment has been
disconnected from mains.
Using VLT
6002 - 6005, 200-240 V: Wait at least 4 minutes
Using VLT
6006 - 6062, 200-240 V: Wait at least 15 minutes
Using VLT
6002 - 6005, 380-460 V: Wait at least 4 minutes
Using VLT
6006 - 6072, 380-460 V: Wait at least 15 minutes
Using VLT 6102 - 6352, 380-460 V: Wait at least 20 minutes
Using VLT 6400 - 6550, 380-460 V: Wait at least 15 minutes
Using VLT
6002 - 6006, 525-600 V: Wait at least 4 minutes
Using VLT
6008 - 6027, 525-600 V: Wait at least 15 minutes
Using VLT
6032 - 6072, 525-600 V: Wait at least 30 minutes
Using VLT
6102 - 6402, 525-600 V: Wait at least 20 minutes
MG.60.C8.02 - VLT is a registered Danfoss trademark
3
Page view 2
1 2 3 4 5 6 7 8 ... 27 28

Comments to this Manuals

No comments