Danfoss TripleLynx CN Installation Manual Page 25

  • Download
  • Add to my manuals
  • Print
  • Page
    / 33
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 24
1) According to FprEN 50524.
2) For fixed systems with semi-optimal conditions.
3) At identical input voltages. At unequal input voltages, V
mppmin
can be as low as 250 V depending on total input power.
4) SPL (Sound Pressure Level) at 1.5m.
5) Grid Management Box (TLX CN Pro and TLX CN Pro+) or third-party product.
5.2. Norms and Standards
Refer to Chapter 1, section
Conformity
for details.
5.3. Installation
Parameter Specification
Temperature
25 °C - +60 °C (>45 °C derating)
Environmental class according to IEC IEC60721-3-3
3K6/3B3/3S3/3M2
Air quality ISA S71.04-1985
Level G2 (at 75 % RH)
Coastal, heavy industrial and farmer areas Must be measured and classified acc. to ISA S71.04-1985
Vibration 1G
Ingress protection class 54
Max. operating altitude 3000 m above sea level.
PELV protection is effective up to 2000 m above sea level only.
Installation Avoid constant stream of water.
Avoid direct sunlight.
Ensure adequate air flow.
Mount on non-flammable surface.
Mount upright on vertical surface.
Prevent dust and ammonia gases.
Table 5.2: Conditions for Installation
Parameter
Condition Specification
Wall Plate Hole diameter 30 x 9 mm
Alignment Perpendicular ± 5° all angles
Table 5.3: Wall Plate Specifications
5. Technical Data
24 L00410580-01_02
5
Page view 24
1 2 ... 20 21 22 23 24 25 26 27 28 29 30 31 32 33