Danfoss VLT 8000 AQUA Operations Instructions Page 40

  • Download
  • Add to my manuals
  • Print
  • Page
    / 44
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 39
39
MG.60.N2.02 - VLT is a registered Danfoss trademark
VLT
®
5000 / VLT
®
6000 HVAC / VLT
®
8000 AQUA
Parameter
Descriptions
803
Bus time out
Selection:
1 - 99 sec 1 sec
Function:
Sets the duration for the bus time out function.
If the set time passes without the drive
receiving a LonWorks message addressed to
Factory setting
it, the drive will take the action specified in
parameter 804,
Bus Time Out Function.
NOTE
After time out counter is reset it
must be triggered by valid control
word before new time out can be
activated.
VLT 5000 parameters are shown in parenthesis, where applicable.
Parameter
List
In addition to the parameters listed above, the
drive's control terminals issue digital inputs
that control functions similar to those provided
by nviStartStop, nviResetFault, and
nviControlWord. Parameters (502) 503
through 508 determine how the drive
responds to commands for (quick stop,
VLT 5000 only), coasting stop, DC brake,
start, reverse, setup select and preset
reference select. See
Network Drive Control
Input
in this manual and the
VLT Instruction
Manual
for more information.
Conversion Data
PNU Parameter Description Default Value Range Index Type
803 Bus time out 1 sec 1 - 99 sec. 0 3
804 Bus time out function no function 0 3
805 Bit 10 function Bit 10 = > CTW ACT 0 6
927 Parameter edit Enable 0 6
928 Process control Enable 0 6
970 Edit setup Active Setup 0 5
971 Store data values no action 0 5