InstallationGuideECLComfort210/310,applicationA214/A314
5.3DuctTlimit



In.-max.(ducttemp.limitation,max.)
11182
CircuitSettingrange
Factorysetting
1
–30.0...0.0-2.0
DetermineshowmuchthedesiredowtemperatureatS3willbeinuenced
(decreased)iftheactualducttemperatureishigherthanthedesiredduct
temperature(Pcontrol).
-30.0:

-2.0:

0.0:

In.-min.(ducttemp.limitation,min.)
11183
CircuitSettingrange
Factorysetting
1
0.0...30.02.0
DetermineshowmuchthedesiredowtemperatureatS3willbeinuenced
(increased)iftheactualducttemperatureislowerthanthedesiredduct
temperature(Pcontrol).
0.0:

2.0:

30.0:

Adapt.time(adaptiontime)
11015
CircuitSettingrange
Factorysetting
1
OFF/1...50sOFF
Controlshowfasttheactualducttemperatureadaptstothedesiredduct
temperature(Icontrol).
OFF:


1:

50:





