Contents1 Copyright3Copyright 3Copyright, Limitation of Liability and Revision Rights 32 Safety5Safety 53 Introduction7Introduction 74 How to install1
4 How to install VLT® FC 100 LonWorks10MG.11.E2.02 - VLT® is a registered Danfoss trademark4
4How to install4.1 How to install4.1.1 The LonWorks OptionThe LonWorks option is equipped with two termination switches, S300 and S301, enabling doubl
4.1.3 Network TerminationDependent on the type of topology, at least one of the connected nodes must be terminated (52.5Ω). The option has two built-
4.1.4 Connecting the Bus LineConnect bus wire NET A to terminal 79 and NET B to 80 of the terminal connector.Terminal Connection79 NET A*80 NET B*61
4.1.7 EMC PrecautionsThe following EMC precautions are recommended in order to achieve interference-free operation of the LonWorks network. Additional
4.1.8 LED BehaviourMS: Service LED (red)Situation LED DescriptionConfigured state (Nornal operation) ½ sec. ON, then continously OFF The node is confi
4.1.9 How to Install Option in Frequency ConverterItems required to install a fieldbus option in the frequency converter:- The fieldbus option- Fieldb
Instructions:- Remove LCP panel from the FC 100- Remove the frame located beneath and discard- Push the option into place. Two positions are possible,
5 Configuration of the system VLT® FC 100 LonWorks18MG.11.E2.02 - VLT® is a registered Danfoss trademark5
5 Configuration of the system5.1 Configuring the System5.1.1 How to Configure the LonWorks NetworkThe LonWorks option card contains a Neuron chip with
Extended status words 60Reference Scaling - Examples 61Network Variables - Overview 62Index64Contents VLT® FC 100 LonWorks2MG.11.E2.02 - VLT® is a reg
5.1.3 FC VSD ProfileThe FC VSD Profile describes all Danfoss VLT specific network variables.Input variablesVariable Function Variable Name SNVT type P
Output variablesVariable function Variable name SNVT type Profile FC 100 par.Status word nvoStatusword SNVT_state FC VSD 16-03Drive output [%] nvoOutp
5.2 Network Variable Description5.2.1 - FC VSD Profile - inputStart/StopVariablename:SNVTtype:State: Value: Command:nviStartStop SNVT_switch 0 (False)
Reference [%]Variablename:SNVTtype: Value: nviRefPcnt SNVT_lev_percent Min. Max. Resolution: -163.840 % +163.830 % 0.005 %This variable sends the
Digital / Relay OutputsVariablename:SNVTtype:State:nviDigitOutput SNVT_state_64 Boolean 1 bit x 64This variable controls the state of the digital outp
Analog Output (X30 / 8)Variablename:SNVTtype: Value: nvi101AnOut1 SNVT_lev_percent Min.: Max.: Resulution: 0 % 100 % 0.01 %NB!This output variabl
These variables contain the value allocated to the analog output terminal X42/7-11 of the Analog I/O option. The variable type is changeable with thec
5.2.2 Network variable description - FC VSD Profile - outputStatus WordVariable name: SNVT type: State:nvoStatusWord SNVT_state Boolean 1 bit x 16This
DC Link Voltage [V]Variablename:SNVTtype: Value: nvoDCVoltage SNVT_volt Min. Max. Resolution: 0 V 10,000 V 0.1 VThis variable contains the measure
Alarm FlagVariablename:SNVTtype:State: Value: Command:nvoAlarm SNVT_switch 0 (False) 0 No alarm(s) present 1 (True) 100 Alarm(s) presentThis variab
1Copyright1.1 Copyright1.1.1 Copyright, Limitation of Liability and Revision Rights This publication contains information proprietary to Danfoss. By a
Extended Status WordVariablename:SNVTtype:State:nvoExtendedStatusword SNVT_state_64 Boolean 1 bit x 64This variable contains the complete extended sta
Analog Input (54)Variablename:SNVTtype: Value: nvoAnIn1 Changeable Min. Max. Resolution: SNVT_volt 0 V 10 V 0.1 VSNVT_amp_mil 0 mA 20 mA 0.1 mASNVT_l
Analog Input (X42/1)Variablename:SNVTtype: Value: nvo109AnIn1 Changeable Min. Max. Resolution: SNVT_volt 0 V 10 V 0.1 VSNVT_temp_p -273.15 °C 327.66
ECB Option StatusVariablename:SNVTtype:State:nvoECBStatus SNVT_state Boolean 1 bit x 16This variable displays the current status of the ECB option.Bit
5.3 VSD 6010 Profile5.3.1 IntroductionThe Variable Speed Drive 6010 profile is a LonMark standardized functional profile.It describes how to control a
5.3.4 Configuration Properties (nci)Variable function Variable name SNVT type ProfileFC 100 pa-rameterMax. motor speed [%] nciMaxSpeed SNVT_lev_percen
5.5 Network Variable Description - VSD Profile - Output5.5.1 Drive SpeedVariablename:SNVTtype: Value: nvoDrvSpeed SNVT_lev_percent Min: Max: Resolut
5.6 Network Variable Description - VSD Profile - Configuration5.6.1 Max Motor Speed [%]Variablename:SNVTtype:Default value: Min value: Max value:nciMa
5.6.5 Min Ramp-up Time [s]Variablename:SNVTtype:Default value: Min value: Max value:nciRampUpTime SNVT_time_sec 10 s 1 s 3,600 sThis variable configu
5.7 Node Object5.7.1 Node ObjectThese variables are used for controlling all functional blocks via the com-missioning tool. 5.7.2 Object RequestVariab
2 Safety VLT® FC 100 LonWorks4MG.11.E2.02 - VLT® is a registered Danfoss trademark2
5.8 Network Timer Functions5.8.1 Control Word Time-out Functionpar.8-03 Control Timeout Time and par.8-04 Control Timeout Function provide a means for
6 How to control the Frequency Converter6.1 How to Control the FC 1006.1.1 Reference HandlingSelect the frequency converter configuration mode in par.
6.2 Danfoss FC Control Profile6.2.1 FC Control ProfileControl Word According to FC Profile(Par. 8-10 set to FC Profile)Bit Bit value=0 Bit value=100 R
Bit 06, Ramp stop/start:Bit 06 set to [0] causes a stop, in which the motor speed is ramped downto stop via the selected ramp down parameter.Bit 06 se
6.2.4 Explanation of the Status BitsBit 00, Control not ready / ready:Bit 00 set to [0] means that the frequency converter has tripped.Bit 00 set to
7 How to access FC 100 parameters7.1 User-defined Network Variables UNVT7.1.1 UNVT Parameter structureTwo special User-defined Network Variables (UNVT
7.1.2 UNVT examplesExample: Read parameter 3-41Ramp 1 Ramp-up TimeIn the LonMaker browser, select the nviParamRequest and choose [Details].130BA452.10
In the bottom window, select the function [READ_VALUE].130BA451.10VLT® FC 100 LonWorks 7 How to access FC 100 parametersMG.11.E2.02 - VLT® is a regist
In the [Field List:] under the section [par_number], enter the parameter number (in this example 3-41). If an indexed (array) parameter is accessed, t
8 Parameters8.1 Parameter list8.1.1 Parameter listPar. No. Parameter name: Default value: Range:Conversiontype:Data type:8-01 Control Site Dig. and co
2Safety2.1 Safety2.1.1 Safety noteThe voltage of the frequency converter is dangerous whenever connected to mains. Incorrect installation of the motor
[2] USB Port[3] * Option A[4] Option B[5] Option C0[6] Option C1NB!This parameter cannot be adjusted while the motor is running.8-03 Control Timeout
8-05 End-of-Timeout FunctionOption: Function:Select the action after receiving a valid control word following a time-out. This parameter is activeonl
[1] Bus[2] Logic AND[3] * Logic ORNB!This parameter is active only when par.8-01 Control Site is set to [0] Digital and control word.8-52 DC Brake Se
NB!This parameter is active only when par.8-01 Control Site is set to [0] Digital and control word.8-55 Set-up SelectOption: Function:Select control
8.3 Parameter Group 1111-00 Neuron IDRange: Function:View the Neuron chip's unique Neuron ID number.0 N/A* [0 - 0] View the Neuron chip's
8.4 Data Types Supported by FC 1008.4.1 Object and Data Types Supported by FC 100Datatype:Description:3 Integer 164 Integer 325 Unsigned 86 Unsigned 1
9 Troubleshooting VLT® FC 100 LonWorks56MG.11.E2.02 - VLT® is a registered Danfoss trademark9
9 Troubleshooting9.1 Alarm-, Warning and Extended Status Word9.1.1 Alarm and warning messagesGeneralThere is a clear distinction between alarms and wa
9.1.2 Alarm wordsAlarm word, par. 16-90 Alarm WordBit(Hex)Alarm Word(par. 16-90 Alarm Word)00000001 Brake check00000002 Power card over temperature000
9.1.3 Warning wordsWarning word , par. 16-92 Warning WordBit(Hex)Warning Word(par. 16-92 Warning Word)00000001 Brake check00000002 Power card over tem
2.1.2 Safety Regulations1. The frequency converter must be disconnected from mains if repair work is to be carried out. Check that the mains supply ha
9.2 Extended Status Word9.2.1 Extended status wordsExtended status word, par. 16-94 Ext. Status WordBit(Hex)Extended Status Word(par. 16-94 Ext. Statu
9.3 Reference Scaling - Examples9.3.1 Reference Scaling - Open LoopExample:par. 3-02 Minimum Reference = 100 RPMpar. 3-03 Maximum Reference = 1500 RPM
9.4 Network Variables - Overview9.4.1 Output variables (nvo)Variable function Variable name SNVT type Profile FC 100par.Status word nvoStatusword SNVT
9.4.2 Input variables (nvi)Variable Function Variable Name SNVT type Profile FC 100 par.Start/Stop nviStartStop SNVT_switch FC VSD CTW/referenceContro
IndexAAbbreviations 9About This Manual 7Alarm And Warning Messages 57Alarm Flag 29Alarm Word 58Alarm Word 29Analog Input (53) 30Analog Input (54) 31An
Extended Status Word 30Extended Status Word 2 60FFanbelt Broken 28Fc Control Profile 42Fc Vsd Profile 20Fc Vsd Profile - Input 22Fieldbus Option 16Fre
Output Variables (nvo) 62Output Voltage 36PParameter Access Command 26Parameter Access Response 33Parameter List 49Preset Reference Select 8-56 53QQue
3Introduction3.1 Introduction3.1.1 About this manualFirst time users can obtain the most essential information for quick installation and set-up in th
3.1.5 Background KnowledgeThe Danfoss LonWorks Option Card is designed to communicate with any system complying with the FTT and 78Kbps LonWorks stand
3.1.8 AbbreviationsACK AC KnowledgeA AmpereBOOL BooleanCC Control CardCTW Control WordEMC Electromagnetic CompatibilityFTT Free Topology TransceiverHF