VLT
®
2800 Series
Quick
Setup
Quick Setup
General warning
Using this Quick Setup, you can carry out quick and
EMC-correct installation of the frequency converter
in five steps. The Operating Instructions, which are
also enclosed, give other examples of installation
and describe all functions in detail.
Read the safety instructions on the next
page before installing the unit.
Mechanical Installation
VLT 2800 frequency converters allow side-by-side
installation. Because of the need for cooling, there
must be 10 cm free air passage above and below
the frequency converter. Drill holes in accordance
with the measurements given in section Mechanical
dimensions. Retighten all four screws.
Fit the decoupling plate to the power cables and
the earth screw (terminal 95).
Electrical Installation, power
Please note that the power terminals can be removed.
Connect mains to the mains terminals of the frequency
converter, i.e. 91, 92, 93 and the earth connection to
terminal 95. Fit a screened/armoured cable from the
motor to the motor terminals of the frequency converter,
i.e. U, V, W. The screen ends in a screen connector.
Electrical Installation, control cables
Remove the front cover underneath the control panel.
Place a jumper between terminals 12 and 27.
Programming
Carry out programming on the control panel. Press
the [QUICK MENU] key to enter the Quick menu. In
this menu, parameters can be selected by means of
the [+] and [-] keys. The parameter values can be
changed by pressing [CHANGE DATA]. Changes are
programmedusingthe[+]and[-]keys. Finishthe
change of a parameter setting by pressing [CHANGE
DATA]. A change of parameter values is saved
automatically after a mains failure. If the display shows
three dots at the right, the parameter value has more
than three digits. In order to see the value, activate
[CHANGE DATA]. Press [QUICK MENU]: Set the motor
parameters that are on the nameplate of the motor:
Motor power [kW] parameter 102
Motor voltage [V] parameter 103
Motor frequency [Hz] parameter 104
Motor current [A] parameter 105
Rated motor speed parameter 106
Activate AMT:
Automatic motor tuning parameter 107
Set reference range
Min. reference, Ref
MIN
parameter 204
Max. reference, Ref
MAX
parameter 205
Ramp-up time [s] parameter 207
Ramp-down time [s] parameter 208
In parameter 002 Local/remote control, the frequency
converter mode can be selected as Remote
MG.28.A9.02 - VLT is a registered Danfoss trademark