Mixing control, 230 V a.c. and 24 V a.c.
DH-SMT VD.7A.A6.02 © Danfoss 07/2004 1
Application
Functions
Application example
The ECL Comfort 100M is a controller for weather
compensation of the flow temperature in directly
or indirectly connected district heating systems
or in boiler systems with mixing valve.
The ECL Comfort 100M controller has triac
outputs for motorized valve control and relay
output for pump control.
Temperature sensors for flow temperature,
outdoor and room temperature can be
connected.
The enclosure is designed for wall and panel
mounting.
It is possible to connect an outdoor sensor
as well as a room sensor. The outdoor sensor
enables weather compensation, and with the
room sensor, a reference room control function
is obtainable.
An analog clock can be mounted on the
controller if a reduced temperature is requested.
During reduced temperature operation, the
room/ flow temperature is lowered according
to the outdoor temperature or kept at a fixed
reduced value.
The heating circuit is frost protected at 10 °C by
the flow temperature during stand-by.
The circulation pump is controlled according to
reference temperature. The pump is ON when
Tref > 20 °C or Tout < +2 °C.
Each of the minimum and maximum flow
temperatures can be set to one of two values.
The neutral zone and control parameters are
factory set. The running time of the motorized
valve can be set to short or long.
The controller can be used as a slave in systems
with master/slave controllers. The controller is
addressed with DIL switches.
The room panel ECA 60 / 62* or the remote
control ECA 61 / 63* can be connected to the
system device bus.
* ECA 62 and ECA 63 have humidity sensors
Page view 0
1 2 3 4

Summary of Contents

Page 1 - ECL Comfort 100M

Data sheetECL Comfort 100MMixing control, 230 V a.c. and 24 V a.c.DH-SMT VD.7A.A6.02 © Danfoss 07/2004 1 ApplicationFunctionsApplication exampleTh

Page 2 - Data sheet ECL Comfort 100M

2 VD.7A.A6.02 © Danfoss 07/2004 DH-SMT Data sheet ECL Comfort 100MOrderingOperationType Designation Code no.ECL Comfort 100M Controller - 230 V a

Page 3

DH-SMT VD.7A.A6.02 © Danfoss 07/2004 3 Data sheet ECL Comfort 100MRange Factory settingHeating curve (H) 0.2 to 2.2 1.2Parallel displacement +/-8

Page 4

4 VD.7A.A6.02 © Danfoss 07/2004 DH-SMT Data sheet ECL Comfort 100MDimensionsCut-out for mountingMounting in a panel (connector set, code no. 087B