Danfoss DHP-H User Manual Page 6

  • Download
  • Add to my manuals
  • Print
  • Page
    / 22
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 5
6
Technicaldata
VFBMC402
1905
1620
Space requirement
Sensors
Outdoor sensor Other sensors
°C
kohm
°C
kohm
-30 1884 0 66,3
-25 1443 5 52,4
-20 1115 10 41,8
-15 868 15 33,5
-10 681 20 27,1
-5 538 25 22,0
0 428 30 18,0
5 343 35 14,8
10 276 40 12,2
15 224 45 10,1
20 183 50 8,5
25 150 55 7,1
30 124 60 6,0
35 103 65 5,0
40 86 70 4,2
75 3,7
80 3,1
85 2,7
90 2,3
95 2,0
Necessaryservicespaceandminimumheadroomforheatpumpinstallation.