Alternative fuses 380-500 V drives
VLT
2800
Buss-
mann
E52273
Buss-
mann
E4273
Buss-
mann
E4273
Buss-
mann
E4273
Buss-
mann
E4273
Buss-
mann
E4273
SIBA
E18027
6
Little
Fuse
E81895
Ferraz-
Shaw-
mut
E16326
7/E2137
Ferraz-
Shaw-
mut
E16326
7/
E2137
RK1/
JDDZ
J/JDDZ T/JDDZ CC/JDDZ CC/JDDZ CC/JDDZ RK1/
JDDZ
RK1/
JDDZ
CC/JDDZ RK1/
JDDZ
2805-
2820
KTS-R20 JKS-20 JJS-20 FNQ-
R-20
KTK-R-20 LP-CC-20 5017906-
020
KLS-R20 ATM-R25 A6K-20R
2855-
2875
KTS-R25 JKS-25 JJS-25 5017906-
025
KLS-R25 ATM-R20 A6K-25R
2880-
2882
KTS-R50 JKS-50 JJS-50 5014006-
050
KLS-R50 - A6K-50R
Alternative Fuses 200-240 V drives
2803-
2822
KTN-R20 JKS-20 JJN-20 5017906-
020
KLS-R20 ATM-R25 A6K-20R
2840 KTN-R25 JKS-25 JJN-25 5017906-
025
KLS-R25 ATM-R20 A6K-25R
Table 1.4: Prefuses for UL application /cUL
1.4.14 RFI switch
Mains supply isolated from earth:
If the frequency converter is supplied from an isolated mains source ( IT mains) or TT/TN-S mains
with grounded leg, the RFI switch is recommended to be turned off (OFF). For further reference,
see IEC 364-3. In case optimum EMC performance is needed, parallel motors are connected or
the motor cable length is above 25 m, it is recommended to set the switch in ON position.
In OFF position, the internal RFI capacities (filter capacitors) between the chassis and the inter-
mediate circuit are cut off to avoid damage to the intermediate circuit and to reduce the earth
capacity currents (according to IEC 61800-3).
Please also refer to the application note
VLT on IT mains
, MN.90.CX.02. It is important to use
isolation monitors that are capable for use together with power electronics (IEC 61557-8).
NB!
The RFI switch is not to be operated with mains connected to the unit. Check that
the mains supply has been disconnected before operating the RFI switch.
The RFI switch disconnects the capacitors galvanically from ground.
The switch Mk9, placed next to terminal 96, should be removed to disconnect the RFI-filter.
The RFI switch is only available on VLT 2880-2882.