Parameter Overwiev
0-XX Operation/Display
0-01 Language
*[0] English
[1] German
[2] French
[3] Danish
[4] Spanish
[5] Italian002 Local/Remote Operation
*[0] Remote operation
[1] Local operation
003 Local Reference
If par. 013 = [1] or [2]: 0 - f
MAX
, *50 Hz
If par. 013 = [3] or [4]: Ref
MIN
- Ref
MAX
, *0.0
004 Active Set-up
[0] Factory Set-up
*[1] Set-up 1
[2] Set-up 2
[3] Set-up 3
[4] Set-up 4
[5] Multi Set-up
005 Programming Set-up
[0] Factory Set-up
*[1] Set-up 1
[2] Set-up 2
[3] Set-up 3
[4] Set-up 4
*[5] Active Set-up
0-06 Set-up Copying
*[0] No copying
[1] Copy to Set-up 1 from #
[2] Copy to Set-up 2 from #
[3] Copy to Set-up 3 from #
[4] Copy to Set-up 4 from #
[5] Copy to all set-ups from #
007 LCP Copy
*[0] No copying
[1] Upload all parameters
[2] Download all parameters
[3] Download size-independent parameters
008 Display Scaling of Output Frequency
0.01 - 100.00, *1.00
009 Large Diplay Readout
[0] No readout
[1] Resulting reference [%]
[2] Resulting reference [unit]
[3] Feedback [unit]
*[4] Frequency [Hz]
[5] Output frequency x scaling
[6] Motor current [A]
[7] Torque [%]
[8] Power [kW]
[9] Power [HP]
[11] Motor voltage [V]
[12] DC link voltage [V]
[13] Thermal load motor [%]
[14] Thermal load [%]
[15] Running hours [Hours]
[16] Digital input [Bin]
[17] Analog input 53 [V]
[19] Analog input 60 [mA]
[20] Pulse reference [Hz]
[21] External reference [%]
[22] Status word [Hex]
[25] Heatsink temperature [°C]
[26] Alarm word [Hex]
[27] Control word [Hex]
[28] Warning word [Hex]
[29] Extended status word [Hex]
[30] Communication option card warning
[31] Pulse count
010 Small Display Line 1.1
See par. 009.
*[17] Analog input 53
011 Small Display Readout 1.2
See par. 009.
*[6] Motor Current [A]
012 Small Display Readout 1.3
*See par. 009.
*[3] Feedback [unit]
013 Local Control
[0] Local not active
[1] Local control and open loop without slip com-
pensation
[2] Remote-operated control and open loop without
slip compensation
[3] Local control as par. 100
*[4] Remote-operated contorl as par. 100014 Lo-
cal stop
[0] Not active
*[1] Active
015 Local Jog
*[0] Not active
[1] Active
016 Local Reversing
*[0] Not active
[1] Active
017 Local reset of Trip
[0] Not active
*[1] Active
018 Lock for Data Changes
*[0] Not locked
[1] Locked
019 Operating Mode at Power-up, Local Op-
eration
[0] Auto re-start, use saved reference
*[1] Forced stop, use saved reference
[2] Forced stop, set ref. to 0
020 Hand Operation
*[0] Not active
[1] Active
024 Userdefined Quick Menu
*[0] Not active
[1] Active
025 Quick Menu Set-up
Value 0 - 999, *000
Load and Motor
100 Configuration
*[0] Speed control, open loop
[2] Speed control, closed loop
[3] Process control, closed loop
101 Torque Characteristic
*[1] Constant torque
[2] Variable torque low
[3] Variable torque medium
[4] Variable torque high
[5] Variable torque low with CT start
[6] Variable torque medium with CT start
[7] Variable torque high with CT start
[8] Special motor mode
102 Motor Power P
M,N
0.25 - 22 kW, *Dep. on unit
103 Motor Voltage U
M,N
For 200 V units: 50 - 999 V, *230 V
For 400 V units: 50 - 999 V, *400V
104 Motor Frequency f
M,N
24 - 1000 Hz, *50 Hz
105 Motor Current I
M,N
0.01 - I
MAX
, Dep. on motor
106 Rated Motor Speed
100 - f
M,N
x 60 (max. 60000 rpm), Dep. on par. 104
107 Automatic Motor Tuning, AMT
*[0] Optimisation off
[1] Optimisation on
108 Stator Resistance R
S
0.000 - x.xxx Ω, *Dep. on motor
109 Stator Resistance X
S
0.00 - x.xx Ω, *Dep. on motor
117 Resonance Damping
OFF - 100%
*OFF%
119 High Start Torque
0.0 - 0.5 s * 0.0 s
120 Start Delay
0.0 - 10.0 s * 0.0 s
1 Quick Guide VLT 2800 Quick Guide
22
MG.28.M1.02 - VLT
®
is a registered Danfoss trademark
1