10 Installation guide RI8BP602 © Danfoss 10/2011 AKM/AK Monitor/AK Mimic
4. Connection to AK-SC 255, AK-SC 355, AK-CS, AK-SM 720 / 350
Introduction
This section describes the functions that relate to the AKM and:
• AK-SC 255 version 02_121 or newer.
• AK-SC 355 version
• AK-CS version 02_121 or newer.
• AK-SM 720 and AK-SM 350
For further information on setups, see the relevant instruction
manuals.
This section describes the installation of the AK-SC 255. Other
units can be installed in the same way, apart from one instance,
which will be explained.
Setting
1. Start Plant Archive
Access to Plant Archive is via the function lowest on the right of
the screen display screen or via the "F5" key.
Information
Once a connection has been established to a plant via this function, the
connection will be saved, even after navigating through the different
menus in the AKM program. The connection is deactivated by:
• Selecting "Close connection"
• "Log out"
Two minutes without data transmission (the time can be adjusted). If
contact is broken for this reason, the connection will automatically be
re-established when a function requiring communication is activated.
Info
The AKM can:
• Load log data
• Receive alarms
The AK-SC 255, AK-SC 355 and AK-CS can also:
• Upload and change Master Control settings
• Create Mimic menus and objects
• Change parameters in the connected controllers.
To communicate between AKM and AK-SC 255/AK-SC 355/AK-CS, the fol-
lowing conditions must be met:
1. Alarms must be routed to the AKM PC in XML format
2. "Authentication Code" and "Account number" with editing rights (Su-
pervisor Access) must be accessible.
(The factory settings are: Auth. Code = 12345, and Account = 50)
3. AK-SC 255/355/CS must have the web function activated, and internal
websites must be installed. The sites contain interfaces that are used by
AKM.
Information
Plant Archive is built up in a DSN structure (Domain,
Subnet and Network). There are a total of 63
domains, 255 subnets and 255 networks. A given
number of plants can be added to the archive,
though the first 255 (00.000.xxx) are dedicated to
plants using Gateways (e.g. AKA 245).
If you can see the plant in the display before you
have set the DSN number, it is because the AKM has
received an alarm from the plant and has had to set
a default DN address.
If this address is to be changed, this must be
done now before continuing setup, otherwise
it will be connected to the settings for Logs and
Mimic.
- Stop alarm sending in the AK-SC 255.
- Continue setup on next page.
(Remember to restart the alarm send at a later time.)