22 Installation guide RI8BP602 © Danfoss 10/2011 AKM/AK Monitor/AK Mimic
Appendix 3 - continued
Situation 1
Preparation of system for data communication
Objective
• All units of the data communication link must be started, so that
the system will be ready for programming.
Conditions
• New installation
• All controllers must be energised
The data communication cable must be connected to all control-
lers
The data communication cable must be installed in accordance
with the instructions “Data Communication Cable for ADAP-
KOOL® Refrigeration Controls” (literature No. RC0XA)
Procedure
1. Check that the data communication cable connections are cor-
rect:
a) H to H and L to L
b) That the screen is mounted at both ends and that the screen
does not touch the frame or other electric connections (not
either the earth connection, if there is one)
c) That the cable is correctly terminated, i.e. that the “first and
“last” controllers are terminated.
2. Set an address in each controller:
a) In AKC and AKL controllers the address is set by means of a
switch on the unit’s printed circuit
b) In AKA 245 gateway the address is set from control panel
AKA 21
• A master gateway gives address 125
• If there are several gateways on a network, you may only
energise one gateway at a time. Other-wise there will be a
conflict, because all gateways come factory-set with same
address
• Remember to set both network number (1) and address
(125).
• Set the gateway, so that it is defined as a modem gateway
(MDM).
Thereafter activate the function "Boot gateway".
3. Set the clock in AKA 245 master gateway’s address 125. (This is
the clock that sets the clocks in the other controllers).
4. Connect a modem, if applicable.
a) Connect modem and AKA 245 with a serial cable (standard
modem cable)
b) The supply voltage to the modem must be connected via
relay output DO1 on AKA 245 (reset function)
c) Connect the modem to the telephone network.
5. Check that the modem has been installed correctly before leav-
ing the plant. For instance by making a call to or from a central
PC.
5
Modem
Modem-gateway (1:125)
1c
?
2b
1:125