RS485
Terminate the RS485 communication bus at both ends.
To terminate the RS485 bus:
Connect Bias L to RX/TX B
Connect Bias H to RX/TX A
The RS485 address of the inverter is unique, and defined at the factory.
Illustration 5.8: RS485 Communication Detail - Cat 5 T-568A
Pinout RS485
1. GND
2. GND
3. RX/TX A (-)
4. BIAS L
5. BIAS H
6. RX/TX B (+)
7. Not connected
8. Not connected
Bold = Compulsory, Cat5 cable
contains all 8 wires
For Ethernet: 10Base-TX and
100Base-TX auto cross over
Table 5.8: RJ45 Pinout Detail for RS485
Ethernet
Ethernet connection is available for TLX CN Pro and TLX CN Pro+ variants only.
Pinout
Ethernet
Colour Standard
Cat 5
T-568A
Cat 5
T-568B
1. RX+ Green/white Orange/white
2. RX Green Orange
3. TX+ Orange/white Green/white
4. Blue Blue
5. Blue/white Blue/white
6. TX- Orange Green
7. Brown/white Brown/white
8. Brown Brown
Table 5.9: RJ45 Pinout Detail for Ethernet
5. Technical Data