NB!
VLT 2880-2882 do not have the AMT function.
Set reference range
Min. reference, Ref
MIN
Parameter 204
Max. reference, Ref
MAX
Parameter 205
Set ramp time
Ramp-up time [s] Parameter 207
Ramp-down time [s] Parameter 208
In parameter 002,
Local/remote control
, the frequency converter mode can be selected as
Remote
operation
[0], i.e. via the control terminals, or
Local
[1], i.e. via the control unit.
Set the control location to
Local
[1]
Local/remote operation =
Local
[1], Par. 002
Set the motor speed by adjusting the
Local reference
Local reference, Par. 003
1.6 Motor Start
Press [START] to start the motor. Set the motor speed by adjusting par. 003,
Local reference
.
Check whether the direction of rotation of the motor shaft is clockwise. If not, exchange any two
phases on the motor cable.
Press [STOP/RESET] to stop the motor.
Press [QUICK MENU] to return to display mode.
[QUICK MENU] + [+] keys must be pressed simultaneously to give access to all parameters.