Other connections
Large display (Solar-Log500, Solar-Log1000)
Solar-Log
1000/500/200
Installation 137 of 268
Connection through S0 output
If the S0 output is used, only the current feed-in power can be transmitted in
the form of a pulse sequence. The display has to calculate the power output
and total yield by itself.
Depending on the connector assignment in Solar-Log™, the S0 output can be
current-controlled or contact-controlled.
Wiring for a current-controlled S0 output
(Example: display system)
The wiring consists of a 2 pin shielded cable (2 x 0.6 mm²)
(up to 100 m long) and a terminal block connector ( Page 15).
Solar-Log™ S0 In/Out
Terminal
Display
4
jumper
S0+
5
S0-
6
Further information about connection can be obtained from the manufacturer
of the display.
Wiring for a contact-controlled S0 output
(Example: RiCo-Electronic)
The wiring consists of a 2 pin shielded cable (2 x 0.6 mm²)
(up to 100 m long) and a terminal block connector ( Page 15).
Solar-Log™ S0 In/Out
Terminal Solar-Log™ RS485-A/B
Display
6
S0-
5
S0+
Further information about connection can be obtained from the manufacturer
of the display.
Pulse factor
In the standard setting, Solar-Log
1000
sends 1000 pulses/kWh over the S0 output.
The pulse factor must be configured according to the size of the installation (kWp):
Installation size kWp
Pulse factor
30 kWp
2000
60 kWp
1000
100 kWp
600
150 kWp
400
300 kWp
200
600 kWp
100
Note that the pulse factor in the Solar-Log™ must have the same setting as
the connected device.
]