Connecting the inverters
Mitsubishi with RS485 interface
38 of 268 Solar-Log
1000/500/200
Installation
4.10 Mitsubishi with RS485 interface
Overview
Interface integrated
Where to connect: 2 RJ11 sockets inside the inverter.
2 pin wiring
Communication address must be allocated.
Work steps
Switch off the inverters and the SolarLog™; Page 17
Connect inverters to the Solar-Log
Connect the inverters to each other
Allocate communication address
Connecting inverters to the Solar-Log
The wiring is done using the
ready-made RJ11 data cable (optional extra; not supplied)
or
your own fabricated cable connection with RJ11 plug and terminal
block connector ( Page 15)
Procedure
1 Unscrew the front plate of the inverter as shown in the inverter's instruc-
tions.
2 If you are fabricating the cable yourself, connect the wires as shown in the
following diagram:
Solar-Log™ terminal block connector
RJ11 inverter
Terminal
Pin
1
3
4
4
3 Insert the RJ11 plug into any RJ11 socket on inverter 1.
4 If only one inverter is to be connected it must be terminated:
In the inverter set the DIP switch for the terminal resistor to ON.
5 Screw the front plate inverter on again if no other inverters are to be con-
nected.
6 Insert the terminal block connector into the Solar-Log™ RS485 socket.