Connecting the inverters
REFUSOL
50 of 268 Solar-Log
1000/500/200
Installation
Connecting the inverters to each other (Solar-Log
500
, Solar-Log
1000
)
Connect using
a 2 wire shielded data cable and
4 pin SACC-M12MS-4SC plugs (2 supplied with the inverter).
Where to connect: RS485 sockets on the bottom of the inverter.
The RS485 IN and OUT sockets are each double connections so that the
wiring can be continued to the next inverter.
Procedure
1 Connect the data cable to the SACC-M12MS-4SC plug as shown in the
inverter's instructions.
2 Insert one plug into the OUT (X14B) socket of inverter 1.
3 Insert the other end of the wire into the IN socket (X15B) on inverter 2.
4 Connect the other inverters to each other in the same way.
5 Terminate in the last inverter:
On the sockets RS485 OUT with REFUSOL round plugs bypass the con-
nections PIN1 to PIN2 and PIN3 to PIN4.
6 Close inverters.
Allocating communication address
Recommendation: Continuous numbering starting with 1; highest pos-
sible address: 31
Set the following parameters on the inverter's operating display:
1 Press F1, select Numerical list, press ENTER.
2 Set parameter number 2000 [password protection], press ENTER twice.
3 Enter 72555, press ENTER.
4 Set parameter number 0406, press ENTER.
5 Select subparameter 0406,3, press ENTER.
6 Enter figure for communication address x
[x = continuous numbering starting with 1; highest possible address: 31],
press ENTER.
After configuring on the display:
1 Using the installed DC isolating switch turn the inverters on and off briefly
so that the settings are activated.
2 Set the date and time on the inverter as shown in the inverter instructions.