Connecting the inverters
Steca
90 of 268 Solar-Log
1000/500/200
Installation
4.39 Steca
Overview
Interface integrated
Where to connect: RJ45 socket outside on the inverter interface card.
2 pin wiring
Communication address must be allocated.
Work steps
Switch off the inverters and the SolarLog™; Page 17
Connect inverters to the Solar-Log
Connect the inverters to each other
Allocate communication address
Connecting inverters to the Solar-Log
The wiring is done using the
ready-made data cable (optional extra; not supplied)
or
your own fabricated RS485 data cable with RJ45 plug and terminal
block connector ( Page 15)
CAUTION
Risk of damage to the unit!
The Solar-Log™ also has an RJ45 socket, which must never be connected to
the RJ45 socket on the inverter.
Only connect the inverter using the RS485/422 B interface of the
Solar-Log™ or on the Solar-Log
1000
also via the RS485 A interface.
Procedure
1 If you are fabricating the cable yourself, connect the wires as shown in the
following diagram:
Solar-Log™ terminal block connector
RJ45 inverter
Terminal
Pin
1
1
4
2
2 Insert the RJ45 plug into any RJ45 socket on inverter 1.
3 If only one inverter is to be connected it must be terminated:
On the inverter insert the connection plug into the free RJ45 socket.
4 Insert the terminal block connector into the Solar-Log™ RS485 socket.