Connecting the inverters
EKO Energy
Solar-Log
1000/500/200
Installation 107 of 268
4.50 EKO Energy
Overview
Interface integrated
Where to connect: Between the COM round sockets on the outside of
the inverter.
2 pin wiring
Communication address must be allocated.
Work steps
• Switch off the inverters and the SolarLog™; Page 17
• Connect inverters to the Solar-Log™
• Connect the inverters to each other
• Allocate communication address
Connecting inverters to the Solar-Log™
The wiring is done using the
ready-made data cable (supplied with the inverter).
or
a shielded, 2 wire data cable made by yourself and a terminal block
connector ( Page 15).
Procedure
1 If you are fabricating the cable yourself, connect the wires as shown in the
following diagram:
Solar-Log™ terminal block connector
2 Insert the round plug into any COM round socket on the inverter.
3 If only one inverter is to be connected terminate this in accordance with the
inverter instructions.
4 Insert the terminal block connector into the Solar-Log™ RS485 socket.
Connecting the inverters to each other (Solar-Log
500
, Solar-Log
1000
)
Connection using your own fabricated daisy chain cable.
Where to connect: Between the COM round sockets on the outside of
the inverter.