Danfoss TripleLynx CN Installation Manual Page 118

  • Download
  • Add to my manuals
  • Print
  • Page
    / 268
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 117
Connecting the inverters
Omron
118 of 268 Solar-Log
1000/500/200
Installation
4.57 Omron
Overview
Interface integrated
Where to connect: Terminal strip inside the inverter
3 pin wiring
Communication address must be allocated.
Work steps
Switch off the inverters and SolarLog™; (Page 16).
Connect inverters to the Solar Log
Connect the inverters to each other
Allocate communication address
Connecting inverters to the Solar-Log
The wiring is done using the
self-made, shielded 3 wire data cable and terminal block connector
( Page 15)
Procedure
1. Open the inverter as shown in the inverter's instructions.
2. Connect wires as shown in the diagram below:
Solar-Log™ terminal block connector
Inverter
RS485/422 B
Terminal strip TB401
1
Pin 4 Data +
3
Pin 3 GND
4
Pin 5 Data -
3. If only one inverter is to be connected this must be terminated. To do
this a bridge must be inserted on the inverter between pins 9 and 10.
4. Close the inverter if no other inverters are to be connected.
5. Insert the terminal block connector into the SolarLog™ RS485 socket.
Connecting the inverters to each other (Solar-Log
500
, Solar-Log
1000
)
The wiring is done using the
self-made, shielded 3 wire data cable and terminal block connector
( Page 15)
Procedure
1. Open the inverter as shown in the inverter's instructions.
Inverter n
Inverter n+1
Terminal strip TB401
Terminal strip TB401
6
Pin 3 GND
7
Pin 4 Data +
8
Pin 5 Data -