Connecting the inverters
Hyundai HPC-050HT-E and HPC-100HT-E
104 of 268 Solar-Log
1000/500/200
Installation
4.48 Hyundai HPC-050HT-E and HPC-100HT-E
Overview
Interface integrated
Where to connect: RJ45 CN socket on the outside of the inverter.
2 pin wiring
Communication address must be allocated.
Work steps
• Switch off the inverters and the SolarLog™; Page 17
• Connect inverters to the Solar-Log™
• Connect the inverters to each other
• Allocate communication address
Connecting inverters to the Solar-Log™
The wiring is done using the
ready-made data cable (optional extra; not supplied)
or
your own fabricated cable connection with RJ45 plug and terminal
block connector ( Page 15)
CAUTION
Risk of damage to the unit!
The Solar-Log™ also has an RJ45 socket, which must never be connected to
the RJ45 socket on the inverter.
Only connect the inverter using the RS485/422 B interface of the
Solar-Log™ or on the Solar-Log
1000
also via the RS485 A interface.
Procedure
1 If you are fabricating the cable yourself, connect the wires as shown in the
following diagram:
Solar-Log™ terminal block connector
2 Insert RJ45 plug into socket CN on the inverter.
3 If only one inverter is to be connected terminate this in accordance with the
inverter instructions.
4 Insert the terminal block connector into the Solar-Log™ RS485 socket.