Danfoss TripleLynx CN Installation Manual Page 129

  • Download
  • Add to my manuals
  • Print
  • Page
    / 268
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 128
Connecting the inverters
Oelmayer
Solar-Log
1000/500/200
Installation 129 of 268
Connecting the inverters to each other (Solar-Log
500
, Solar-Log
1000
)
Where to connect: Terminal strip behind service cover
2 pin wiring
Procedure
1 Open the inverter as shown in the inverter's instructions.
2 If your have made the cable yourself, connect the wires as shown in the
following diagram:
1. Solar-Log™ terminal block
connector
2. Terminal strip in inverter
3. Terminal
4. RS485 terminal
5. 1
6. A Data +
7. 4
8. B Data -
3 Connect terminals A and B on inverter 1 to the corresponding terminals on
inverter 2.
4 Connect the other inverters to each other in the same way.
5 Terminate the inverter as shown in the inverter's instructions.
6 Close inverters.
7 Insert the terminal block connector into the Solar-Log™ RS485 socket.
Allocating communication address
Recommendation: Continuous numbering starting with 1.
Setting: Using the solar fitter's menu on the inverter.
Procedure: As set out in the inverter's instructions
Page view 128
1 2 ... 124 125 126 127 128 129 130 131 132 133 134 ... 267 268

Comments to this Manuals

No comments